| WT |
Value |
Measured value to be checked. |
|
|
|
| WT |
Value |
Checked value. If the input value is plausible it is put out unchanged, otherwise the configured behaviour applies. |
| UG |
Invalid |
Becomes 1 as long as the input value is detected as implausible. |
| GR |
Reason |
Reason for the objection:- 0 = valid
- 1 = below minimum
- 2 = above maximum
- 3 = change too large
- 4 = no update
|
|
|
|
|
Minimum |
Smallest plausible value. |
|
Maximum |
Largest plausible value. |
|
Maximum change |
Largest permissible change within the period. 0 = no check. The permissible change is scaled to the interval that has actually elapsed between two values. |
|
Period for change (s) |
Reference period for the maximum change, in seconds. |
|
Monitoring time (s) |
If an update is missing for longer than this time, the value is considered invalid (reason 4). 0 = no check. Every telegram to the address of the input counts as an update, even if the value stays the same. If the input is only connected internally to another block, only changes of value are detected. |
|
Behaviour when invalid |
- Hold last valid value: the output keeps the value last detected as valid. As long as no valid value has occurred yet, the substitute value is put out.
- Output substitute value: the output is set to the substitute value.
- Pass value through: the input value is put out anyway, only the message is given.
|
|
Substitute value |
Value that is put out for an invalid measured value. |