Overview Projector / Display (PJLink)



This function block controls and monitors projectors and displays via PJLink. PJLink is a cross-vendor standard of the JBMIA (Japan Business Machine and Information System Industries Association) for operation over the network. The block switches the device, selects the input, mutes picture and sound and reports the state, faults and operating hours.

Create one block per device. The controller polls the device cyclically and disconnects immediately afterwards, as the standard requires.

Settings on the device:
  • Assign a fixed IP address. The device must be reachable from the controller on TCP port 4352.
  • Enable the PJLink function. On some devices it is off by default.
  • Leave the network on in standby (the name varies by device, e.g. "network standby" or "standby mode: communication on"). Otherwise the device cannot be switched on over the network and counts as unreachable in standby. An energy-saving setting often turns off the network in standby.
  • If a PJLink password is set on the device, enter the same one in the block. Where it is set, and whether there is a default, is stated in the manual of the device.
Setup — step by step:
  1. Insert the block and enter the IP address and, if necessary, the password in the properties.
  2. Test the connection with the Check device button (the controller must be connected). The dialog shows the manufacturer, model and PJLink class as well as the inputs with their number for input QU. Many devices report their inputs only when switched on.
  3. Create addresses with the address generation and link the controls to them.
Selecting an input: The number at input QU is the PJLink code of the input: the first digit is the type (1 = RGB, 2 = video, 3 = digital, 4 = storage, 5 = network, 6 = internal), the second the running number. 31 is therefore the first digital input. The manufacturer decides which connector has which number, HDMI 1 can be 31 or 32 depending on the model. Class 2 devices can have inputs with letters: these are given as type × 100 + value, with A = 10 to Z = 35. 3A is therefore 310.

Warm-up and cool-down: A command stays pending until the device can accept it, for at most 5 minutes. If it still cannot be executed after that, output ER shows error code 4. If the device is switched off during warm-up, the command follows after the warm-up; switching on during cool-down follows after the cool-down. Input, picture and sound wait until the device is on, so "on" and an input can be set at the same time. While something is in progress, the block polls every 5 seconds.

After the controller starts, the pending value of an input does not trigger a command, so a restart never switches the device. This also applies to changes in the first 30 seconds after the start and to responses to read requests. Changes made on the device with the remote control are not reverted, the outputs then show the actual state.

Notes:
  • According to the JBMIA, several projectors should not be switched on at the same time because of the inrush current. Set the EA inputs with a delay for this reason.
  • If a second controller or software accesses the device, failed attempts can occur on devices with only one simultaneous connection. Increase the polling interval in that case.
  • Frequent switching on and off can shorten the service life of the lamp.


Inputs

FG
Enable
Optional. Non-zero enables. At 0 no connections are opened and no commands are sent, pending commands expire, ST and PW go to 0. Changes at the other inputs while disabled are not made up for. Not connected: the block counts as enabled.
EA
On/Off
Optional. Every change of value is evaluated: non-zero switches on, 0 switches to standby. Not connected: the block only monitors the device.
QU
Select input
Optional. Every change of value is evaluated: the value is the number of the input (see above), 0 does nothing. Not connected: no switching.
BA
Picture off
Optional. Every change of value is evaluated: non-zero mutes the picture, 0 restores it. If the device has no separate muting, the block switches picture and sound together. Not connected: no picture muting.
TA
Sound off
Optional. Like BA, but for the sound. Not connected: no sound muting.
FZ
Freeze
Optional. Class 2 only. Every change of value is evaluated: non-zero freezes the picture, 0 cancels it. On devices without this function, ER shows error code 3. Not connected: no freeze.
V+
Volume up
Optional. Class 2 only. The change from 0 to non-zero is evaluated: one step louder. In standby the command expires. Not connected: no adjustment.
V-
Volume down
Optional. Like V+, but one step quieter. Not connected: no adjustment.

Outputs

ST
Connection
1 = device responds. 0 only after three failed connections in a row, or immediately if the login is rejected. Short gaps right after switching are normal.
ER
Error code
0 = OK, 1 = no connection, 2 = login rejected (password or method), 3 = command rejected (e.g. input does not exist), 4 = command not possible within the time limit, 5 = device reports an error, 6 = device does not respond according to PJLink. Codes 3 to 5 from a command remain for 60 seconds.
EM
On feedback
1 = switched on or warm-up, 0 = standby, cool-down or no connection.
PW
Operating state
0 = standby, 1 = on, 2 = cool-down, 3 = warm-up. 0 if there is no connection, observe ST.
QA
Active input
Number of the active input, as with QU. Only updated when switched on.
BM
Picture off feedback
1 = picture muted. Some devices cancel muting by themselves when the input or the signal changes, which this output then also shows.
TM
Sound off feedback
1 = sound muted.
FM
Freeze feedback
1 = picture frozen. Class 2 only, otherwise 0.
SG
Collective fault
Highest value of the six faults: 0 = none, 1 = warning, 2 = error.
SL
Fan fault
0 = none, 1 = warning, 2 = error. 0 can also mean that the device does not have this monitoring. This applies to all faults.
SP
Lamp fault
Like SL.
TE
Temperature fault
Like SL.
SD
Cover fault
Like SL. Cover open.
SF
Filter fault
Like SL.
SO
Other fault
Like SL.
LH
Lamp hours
Operating hours of the lamp, with several lamps the highest value. 0 if the device has no lamp or does not count.
FH
Filter hours
Operating hours of the filter. Class 2 only, otherwise 0.
AU
Input resolution
Text, e.g. 1920x1080. Empty without a signal and in standby. Class 2 only.
NM
Name
Name set on the device (text).
HE
Manufacturer
Text.
MO
Model
Text. On the KNX bus, texts are cut off after 14 characters.

Parameters

IP address / host name
Address of the device in the network. IPv4 only.
Port
TCP port of the device (default 4352).
Login
Method if the device requires a login. MD5 (default) is the method of all PJLink devices. SHA-256 only exists from PJLink specification 2.10 of 2024. On devices without SHA-256, ER reports error code 2.
Password
PJLink password of the device, at most 32 letters and digits. Empty if the device does not require a login.
Polling interval
Interval between polls in seconds (5 to 600, default 10). With pending commands and during warm-up and cool-down, the block polls every 5 seconds.
Timeout
Time to wait per response in seconds (default 5). In standby, some devices respond more slowly.
Debug
Additional diagnostic output in the error log. The password is not output.

Manufacturers

The block follows the PJLink standard and is not tailored to individual manufacturers. The following overview is based on information from the manufacturers and the JBMIA, it is not a test by uni-PRO. The individual model is what counts, not every device of a manufacturer supports PJLink. This can change with new firmware. As of October 2026. The Check device button is suitable for checking, as is the product list of the JBMIA, which does not contain all devices, however.
Epson
Class 2 according to the JBMIA list and the Epson documentation. On individual models, picture and sound can only be muted together.
Sharp / NEC
Class 1 and 2 according to the JBMIA list. The network is off by default on the PA, PX and PH series.
Optoma
Class 2 according to the JBMIA list.
Fujifilm
Class 2 according to the JBMIA list and the manufacturer's command list. Commands are only accepted about 60 seconds after switching on.
Panasonic
According to the network guide Class 1 at least on the PT-CW230 series. Check the manual of the model.
Sony
Depends on the model. The Help Guide of the VPL-CWZ10 mentions PJLink, the one of the VPL-GTZ380 does not.
BenQ
Depends on the model. According to BenQ, some models need an administrator password set in the browser beforehand.
Barco
According to the manual specification 2.00 on the series concerned. The function is off by default.
JVC
Class 1 on the LX-WX50 according to the manual.
Casio, Ricoh
Members of the PJLink subcommittee of the JBMIA. Check the model in the manual.
Named by third parties
Canon, Hitachi/Maxell, Christie, InFocus and Mitsubishi are named as PJLink-capable by providers of other control software. We had no information from the manufacturers, so this must be checked on the model.

See also general parameters of all function blocks.