| SO |
Temp. solar |
Temperature solar (collector). Not linked: the block
calculates with 0 °C, the pump stays off. |
PU
|
Temp. buffer bottom
|
Temperature buffer bottom. Not linked: the block
calculates with 0 °C and charges the bottom permanently. This sensor
must be linked. |
PO
|
Temp. buffer top
|
Temperature buffer top. Not linked: the block
calculates with 0 °C and then always charges the top. This sensor must
be linked.
|
PU
|
Pump
digital
|
Pump digital on/off. |
PA
|
Pump
analog 0-100%
|
Pump analog. As an alternative to
control via switching hysteresis, a pump with
analog control can be used at this output.
|
| VP |
Valve buffer top |
Valve switchover buffer charging: 1 = buffer top, 0 = buffer bottom. |
|
Solar
maximum
|
Maximum temperature solar. If the
temperature exceeds this value, the pump is switched off even if the
buffer temperature has not been reached. |
|
Buffer maximum |
Switch-off temperature buffer. If the temperature buffer
top or bottom exceeds this value, the solar pump is switched off. |
|
Hysteresis
solar on
|
Difference between solar and buffer
at which the control becomes active.
|
|
Hysteresis
solar off
|
Difference between solar and buffer
at which the control becomes inactive. |
|
Gain |
Control setting; the higher the value, the faster the
analog output changes with a change in temperature. |