Solar 1
Boiler/Buffer| This
function block realizes a solar control with one
solar circuit and switching between boiler and buffer. Via a
switchover valve, the solar yield is charged into either the boiler or
the buffer. If the solar temperature is higher than the temperature of the respective storage tank by the Hysteresis solar on and its temperature is below its maximum, the valve switches to this storage tank and the pump turns on:
With the pump switched on, the speed is set proportional to the temperature difference: speed in per cent = Gain x (solar temperature - temperature of the storage tank being charged), limited to 0 to 100 %. The value is present at the output Pump analog 0-100%; with the pump switched off it is 0. The control runs once per second. |
Inputs |
||
| BO | Temp. boiler | Temperature boiler. Not linked: the block calculates with 0 °C, the boiler is therefore regarded as cold and is charged preferentially. This sensor must be linked. |
| PU |
Temp. buffer |
Temperature buffer. Not linked: the block calculates with 0 °C. This sensor must be linked. |
| SO |
Temp. solar |
Temperature solar (collector). Not linked: the block
calculates with 0 °C, the pump stays off. |
Outputs |
||
| PU |
Pump
digital |
Pump digital on/off. |
| PA |
Pump
analog 0-100% |
Pump analog. As an alternative to
control via switching hysteresis, a pump with
analog control can be used at this output. |
| VP | Valve buffer | Valve switchover boiler/buffer: 1 = buffer, 0 = boiler. |
Parameters |
||
| Solar
maximum |
Maximum temperature solar. If the temperature exceeds this value, the pump is switched off even if the storage tank temperature has not been reached. | |
| Boiler maximum | Switch-off temperature boiler. If the boiler temperature exceeds this value, boiler charging is ended. | |
| Buffer maximum | Switch-off temperature buffer. If the buffer temperature exceeds this value, buffer charging is ended. | |
| Hysteresis
solar on |
Difference between solar and storage tank
at which the control becomes active. |
|
| Hysteresis
solar off |
Difference between solar and storage tank at which the control becomes inactive. | |
| Gain | Control setting; the higher the value, the faster the analog output changes with a change in temperature. | |
| Boiler priority | If this parameter is active, the boiler is charged first. Only once the boiler maximum is reached is switching to buffer charging performed. | |